Analog Mix

  • 2 analog current inputs (16 bits)
  • 2 analog current outputs (12 bits)
  • Measurement or output range of 0-20 mA and 4-20 mA

For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.

Technical data

Performance data

Supply voltage
+24 V DC (+18-30 V DC)
Supply monitoring
Yes

Analog inputs

Type
Current
Amount
2
Resolution
16 bits
Measuring range
0-20 mA or 4-20 mA
Measuring accuracy
±0,5 % of maximum measurement value
Conversion time all channels
1 ms
Cable break monitoring
Yes
Hardware filter
typically 1 kHz, low pass 3rd order
Software filter
configurable

Analog outputs

Type
Current
Amount
2
Output range
0-20 mA or 4-20 mA
Resolution
12 bits
Refresh time all channels
1 ms
Settling times
50 µs + load * capacitive load (63 % of the end value)
100 µs + 2*load * capacitive load (86 % of the end value)
250 µs + 5*load * capacitive load (99 % of the end value)
Accuracy
±0.5 % of maximum output value

Mechanical properties

Width (mm)
12,5
Height (mm)
104
Depth (mm)
72
Protection type
IP20

Article number / Certification

Item number
20-017-222
Standardization / Certification
UL 508 (E247993)
We MaxUp Your Automation