AI 075

Analog Input

  • 6 analog inputs (±10 V DC/16 bits) or potentiometer inputs (0-100 %/16 bits)
  • 1 KTY/PT1000 temperature input for potentiometer inputs
  • 1 reference output (+10 V DC/15 mA)

For the S-DIAS system, EPLAN Macros are available for simple integration into the control cabinet.

Technical data

Analog inputs

Type
±10 V DC resp. potentiometer 0-100 %
Amount
6
Resolution
16 bits
Measuring range
-10 V ... +10 V or 0-100 % (potentiometer)
Measuring accuracy
±0.3 % of maximum measurement value or ±0.35 % of the maximum value
Cable break monitoring
Yes
Hardware filter
typically 1 kHz, low pass 3rd order
Software filter
configurable

Analog inputs

Type
temperature
Amount
1
Resolution
0.1 °C
Sensor types
KTY10
PT1000
Measuring range
-125 ... +850 °C or 500.6-4575.3 Ω
Measuring accuracy
±0.5 % of maximum measurement value
Cable break monitoring
Yes
Hardware filter
typically 1 kHz, low pass 3rd order
Software filter
10 Hz

Reference outputs

Amount
1
Reference voltage
+10 V DC
Permissible output current
maximum 25 mA (≥ HW version 1.5, TaMAX = 55 °C)
Short-circuit proof
Yes
Accuracy
±0.5 %

Mechanical properties

Width (mm)
12,5
Height (mm)
104
Depth (mm)
72
Protection type
IP20

Article number / Certification

Item number
20-009-075
Standardization / Certification
UL 508 (E247993)
We MaxUp Your Automation
© 2026 SIGMATEK GmbH & Co KG